| UL Fuse Ratings and Classification |
| |
| |
| Class |
Response |
Interrupt(A) |
AC Volt Ratings |
Amp Ratings |
| |
| |
| L |
Time-Delay |
200,000 |
|
600 |
200 |
6,000 |
| |
| RK1 |
Time-Delay |
200,000 |
250 |
600 |
0.1 |
600 |
| |
| RK1 |
Fast-Acting |
200,000 |
250 |
600 |
1 |
600 |
| |
| RK5 |
Time-Delay |
200,000 |
250 |
600 |
0.1 |
600 |
| |
| T |
Fast-Acting |
200,000 |
300 |
600 |
1 |
1,200 |
| |
| J |
Time-Delay |
200,000 |
|
600 |
1 |
600 |
| |
| J |
Fast-Acting |
200,000 |
|
600 |
1 |
600 |
| |
| CC |
Time-Delay |
200,000 |
|
600 |
0.1 |
30 |
| |
| CC |
Fast-Acting |
200,000 |
|
600 |
0.1 |
30 |
| |
| CD |
Time-Delay |
200,000 |
|
600 |
35 |
60 |
| |
| G |
Time-Delay |
100,000 |
|
480 |
0.5 |
60 |
| |
| K5 |
Fast-Acting |
50,000 |
250 |
600 |
1 |
600 |
| |
| H |
Fast-Acting |
10,000 |
250 |
600 |
1 |
600 |
| |
| |
| |
| Source: Canadian Electrical Code and
National Electrical Code |
|
|
| |
|